GrowerSELECT® Installation Manuals Binder

Hog Slat Inc. Newton Grove, NC USA March 2017 12 Air Storm Fans Operation At all times during operation fan orifice should be free of debris. In the event any component of the fan is compromised discontinue use immediately and contact your local Hog Slat representative. Maintenance In order to begin any maintenance or service to the fan, power must be turned OFF and all moving parts must come to a complete STOP before accessing. All parts inside of the fan housing are accessed by removing the exit wire guard and inlet shutter. Once service is complete, clean excessive build-up from parts. Excessive dust and dirt on parts can cause vibration in the propeller and overheating of the motor. Before beginning operation again, ensure that all safeguards are back in place and all foreign objects are free from the area. Performance Hog Slat Inc. takes great pride in supplying our customers with fans that meet or exceed their performance numbers. This is achieved by testing fans from the production line and continually working to maintain consistency in test data. BESS LABS TEST NUMBER 15207 MAY 28, 2015 (WITH CONE) Static Pressure (in.H2O) Airflow (cfm) rpm Volts Amps Watts cfm/Watt 0.00 7400 1103 229.7 2.00 440 16.8 0.05 6990 1096 229.8 2.10 460 15.2 0.10 6620 1088 229.5 2.19 476 13.9 0.15 6200 1081 229.5 2.27 493 12.6 0.20 5670 1072 229.0 2.37 511 11.1 0.25 3180 1074 230.5 2.34 509 6.3 0.30 2680 1055 230.7 2.55 551 4.9

RkJQdWJsaXNoZXIy MTA3MzU=